Running new cable through a Toronto or GTA renovation eventually means securing it to the framing, and stapling is the standard method. The question homeowners get wrong is not whether stapling is allowed — it is how, how often, and with what staple. Get any of those wrong and the cable jacket takes the damage instead of holding it in place. This guide covers the actual support rules.
Yes, NMD90 cable (the Canadian equivalent of Romex) can and typically should be stapled to studs and joists using cable staples specifically listed for non-metallic sheathed cable. The Ontario Electrical Safety Code requires support within 300 mm (about 12 inches) of every box and at intervals not exceeding 1.5 m (about 5 feet) along the run. Use a staple sized to sit flush without pinching the cable jacket — a standard hammer-in cable staple or a proper cable stapler, never a regular office or construction staple gun with generic staples.
Both rules apply together — a long run needs both the box-proximity staple and the interval staples along its length.
Unsupported cable sags over time under its own weight and thermal cycling. That sag brings the cable into contact with sharp stud edges, drywall screw tips, or HVAC ductwork — any of which can slowly abrade the jacket. A properly stapled cable stays exactly where it was installed, with no opportunity to migrate into contact with something that damages it years later. This is the same mechanical-protection principle behind nail plates on cables crossing stud edges.
The stapling defect we correct most often in GTA DIY work is not missing staples — it is overdriven ones. A homeowner using a framing hammer instead of a lighter tack hammer tends to drive the staple hard enough to visibly dent the cable jacket, sometimes deep enough to nick the conductor insulation beneath. If you are stapling your own cable runs, use a lighter hammer and stop the moment the staple sits flush — do not keep swinging until it feels fully seated the way you would with a framing nail.
No more than 1.5 m apart along the run, plus one within 300 mm of every box or fitting.
No. Use staples or clips specifically listed for non-metallic sheathed cable, not a general construction staple gun.
No, the framing supports it there, but exposed runs before and after still need proper support intervals.
Remove it and inspect the jacket for damage. If the jacket is cut through, that section should be replaced rather than left in service.
Yes, when listed for the application. Common on masonry walls where a hammer staple is impractical.